XZ1(AS)

Suitable for indoor, outdoor, direct burial, or conduit applications.

  • Construction standard: HD-603-5X-2.
  • Low Voltage Directive (LVD) compliant: 2014/35/UE
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Cca-s1b-d2-a1.
  • Industrial use / Distribution network.
  • Cable suitable for indoor and outdoor installations, open air, buried or in conduits.
Conductor Aluminium, class 2, based on UNE-EN 60228 and IEC 60228.
Insulation Cross-linked Polyethylene (XLPE), type DIX 3 according UNE HD 603-1.
Filler Ignifugated filler with high fireproof properties
Outer sheath Low Smoke Zero Halogen (LSZH) polyolefin DMO1 type according HD 603-1.
Nominal Voltage 0,6/1 kV C.A.
Voltage Test 3.500 V C.A. (5 minutes)
Maximum conductor temperatures Normal operation 90°C
Short circuit (5sec) 250°C
  • Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
  • Low halogen content according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.
  • Low corrosive gas emission according to EN 60754-2, IEC 60754-2.
  • Low smoke emission according to EN 61034-2, IEC 61034-2.
  • Fire reaction (CPR) Eca.
  • High cold resistance -40°C (fixed and protected installations)
  • Water resistance AD5 (ITX5) according IEC 60529.
  • UV resistance according HD 605.
  • Impact resistance: AG2 Medium severity.
  • Minimum bending radius 15 x OD (during installation)
Section Electric resistance 20°C (Ohm/km) Insulation thickness (mm) Outer sheath thickness (mm) Maximum overall diameter (mm) Weight

(Kg/km)

Minimum bending radius
1X25 1,20 1 1,3 15,5 326 232
1×50 0,641 1 1,3 17,8 440 267
1×95 0,320 1,1 1,4 21,4 657 321
1×150 0,206 1,4 1,4 24,8 887 372
1×240 0,125 1,7 1,5 30,1 1298 452

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.