ROZ1MZ1-K(AS+)
The ROZ1MZ1-K (AS+) cables are those indicated for the connection of measuring, control and signalling instruments. They have a collective screen to avoid interference and reinforcement of galvanized steel wires that confers high mechanical performance. They are used where it is required to guarantee the supply of halogen-free, non-propagating and fire-resistant cables, the supply to emergency equipment such as signalling, smoke extractors, acoustic alarms, water pumps, etc.
- Construction Standard: UNE-EN 50525-3-31.
- Low Voltage Directive (LVD) compliant: 2014/35/UE
- Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Cca-s1b, d1, a1
- DoP Number: C007-ENG- ROZ1MZ1K(AS+)
- RoHS compliant.
- Suitable for Industrial use / Potentially explosion hazard locations (ATEX area).
Conductor: Electrolytic copper, class 5 (flexible), according EN 60228 and IEC 60228.
Insulation: Mica tape + Cross-linked polyethylene (XLPE).
Screen: Aluminum/Mylar
Internal Outer sheath: Halogen free compound.
Armour: Galvanized Steel wire.
Outer sheath: Halogen free compound.
Nominal Voltage: 300/500 V
Nominal test : 1.500 V.ac
Maximum conductor temperatures: Normal operation 90°C Short circuit. Short circuit (5sec) 250°C
- Non-flame propagation according to UNE-EN 60332-1-2, EN 60332-1-2 e IEC 60332-1-2.
- Non-fire propagation according to UNE-EN 60332-3, EN 60332-3 e IEC 60332-3.
- Low halogen content according to UNE-EN 60754, EN 50267 e IEC 60754.
- Low corrosive gas emission according to UNE-EN 60754-2 e IEC 60754-2.
- Low smoke emission according to UNE-EN 61034-2 e IEC 61034-2.
- Fire reaction (CPR) Cca-s1b, d1, a1.
- UV resistance (1 cycle) according to UNE 211605.
- Water absorption resistance.
- High cold resistance.
- Impact and rodent resistance.
- Fire resistance.
- Electromagnetic protection.
Available on request
- Hydrocarbons and oil resistance according to UIC-895 OR.
- UV resistance (> 10 cycles) according to UNE 211605.
- Rated voltage 450/750V.
ROZ1MZ1-K(AS+) 300/500V
| Section | Resistance at 20 °C
(Ohm/km) |
Conductor Class | External diameter (mm) | Weight (kg/m) | CPR |
| 2X1,5 | 13,3 | 5 | 13,2 | 0,34 | Cca-s1b-d1-a1 |
| 3X1,5 | 13,3 | 5 | 13,7 | 0,37 | Cca-s1b-d1-a1 |
ROZ1MZ1-K(AS+) 450/750V
| Section | Resistance at 20 °C
(Ohm/km) |
Conductor Class | External diameter (mm) | Weight (kg/m) | CPR |
| 2X1,5 | 13,3 | 5 | 13,2 | 0,34 | Cca-s1b-d1-a1 |
| 3X1,5 | 13,3 | 5 | 13,7 | 0,37 | Cca-s1b-d1-a1 |
*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.