H07Z1-K (AS)

H07Z1-K (AS)

The H07Z1-K(AS) is a high-performance cable indicated for permanent installations in public premises where low fumes and corrosive gas emission is required in case of fire, such us hospitals, schools, shopping canters, airports, an all those installations where a greater fire protection is required. They are also appropriate for the installations of individual by-passes.

  • Construction Standard: UNE-EN 50525-3-31, EN 50525-3-31, UNE 211002
  • Low Voltage Directive (LVD) compliant: 2014/35/UE
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Cca-s1b, d1, a1
  • DoP Number: C006-ENG-H07Z1K
  • RoHS compliant.

Conductor: Flexible electrolytic copper conductor (Class V) according to UNE-EN 60288
Insulation: Thermoplastic halogen-free material insulation
Nominal Voltage: 450/750 V
Voltage Test: 2.500 V A.C
Maximum conductor temperatures: 70 ºC

  • Non-flame propagation according to EN 60332-1-2, UNE-EN 60332-1-2, IEC 60332-1-2.
  • Non-fire propagation according to EN 60332-3-24, UNE-EN 60332-3, IEC  60332-3.
  • Low halogen content according to UNE-EN 60754, EN 50267 and IEC 60754.
  • Low corrosive gas emission according to UNE-EN 50267, EN 50267 and IEC 60754.
  • Low smoke emission according to UNE-EN 61034, EN 61034 and IEC 61034.
  • Fire reaction (CPR) Cca-s1b, d1, a1.
  • Water absorption resistance.
  • High cold resistance.
  • High flexibility.
Section (mm2) Resistance at 20 °C

(Ohm/km)

Nominal outer diameter (mm) Weight (kg/m) CPR
1X1.5 13.3 2,9 0,02 Cca-s1b-d1-a1
1X2.5 7.98 3,4 0,03 Cca-s1b-d1-a1
1X4 4.95 3,9 0,04 Cca-s1b-d1-a1
1X6 3.3 4,5 0,06 Cca-s1b-d1-a1
1X10 1.91 5,4 0,10 Cca-s1b-d1-a1
1X16 1.21 6,5 0,15 Cca-s1b-d1-a1
1X25 0.78 8,3 0,24 Cca-s1b-d1-a1
1X35 0.554 9,4 0,32 Cca-s1b-d1-a1
1X50 0.386 11 0,46 Cca-s1b-d1-a1
1X70 0.272 12,9 0,65 Cca-s1b-d1-a1
1X95 0.206 14,3 0,85 Cca-s1b-d1-a1
1X120 0.161 16,6 1,07 Cca-s1b-d1-a1
1X150 0.129 19,2 1,36 Cca-s1b-d1-a1
1X185 0.106 21,6 1,66 Cca-s1b-d1-a1
1X240 0.0801 23,9 2,18 Cca-s1b-d1-a1

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.