ROVMV
ROVMV is an I&C cable suitable for areas with a high risk of electromagnetic interference. These cables are indicated for industrial installations with a risk of fire and explosion. The installation of those cables is highly recommended in service stations (gas stations), petrochemical plants, flammable products warehouses, etc. Likewise, it can be used in installations as production plants and in general in all the installations where the cable can be subject to risks interferences, mechanical aggression and fire protection is required.
- Technical designation ROVMV rigid copper conductor class 2.
- Technical designation ROVMV-K flexible copper conductor class 5.
- Construction Standard: UNE -EN-50288-7, IEC-60288.
- Low Voltage Directive (LVD) compliant: 2014/35/UE
- Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Eca.
- RoHS compliant.
- Suitable for Industrial use / Potentially explosion hazard locations (ATEX area).
| Conductor | Rigid electrolytic copper conductor (Class II) or flexible (class V) according to UNE-EN 60288 |
| Insulation | Cross-linked Polyethylene (XLPE), according UNE EN 50288-7 |
| Screen (collective) | Polyester tape + tinned copper drain wire + aluminum/mylar tape with 100% coverage |
| Inner sheath | PVC according EN 50288-7 |
| Armour | Crown galvanized steel wire |
| Sheath | PVC according EN 50288-7 |
| Nominal voltage | 300/500 V |
| Test voltage | 2.000 V.ac |
| Maximum conductor temperatures | Normal operation 90°C Short circuit |
| Short circuit (5sec) 250°C |
- Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
- Fire reaction (CPR) Eca.
- UV resistance (1 cycle) according to UNE 211605 and EN 50289-4-17.
- Suitable for all type of installations withstand damp conditions including immersion in water (AD7).
- High cold resistance, cable designed to operate reliably at -40ºC in fixed installations and protected installations.
- Impact resistance: AG4. High severity.
- Rodent resistance.
AVAILABLE ON REQUEST
- Hydrocarbons and oil resistance according to UIC-895 OR.
- Flexible / rigid conductor according to UNE EN 60228.
- Non-fire propagation according to EN 60332-3-24, IEC 60332-3-24.
- Low halogen content (≤ 14%) according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.
| Section | Resistance at 20 °C
(Ohm/km) |
External diameter (mm) | Weight (kg/m) |
| 2X2X0,5 | 36 | 13,3 | 0,331 |
| 6X2X0,5 | 36 | 16,9 | 0,526 |
| 8x2x0,5 | 36 | 17,9 | 0,567 |
| 12X2X0,5 | 36 | 22,8 | 0,925 |
| 18X2X0,5 | 36 | 26,2 | 1,182 |
| 24X2X0,5 | 36 | 29,3 | 1,412 |
| 6x2x1 | 18,1 | 19,7 | 0.706 |
| 12x2x1 | 18,1 | 26 | 1,211 |
| 24x2x1 | 18,1 | 34,9 | 2,151 |
| 2X1,5 | 12,1 | 11,6 | 0,289 |
| 3X1,5 | 12,1 | 12,4 | 0,333 |
| 4X1,5 | 12,1 | 13,3 | 0,378 |
| 2X2X1,5 | 12,1 | 15,5 | 0,451 |
| 6X2X1,5 | 12,1 | 21,7 | 0,936 |
| 12X2X1,5 | 12,1 | 27,8 | 1,428 |
| 24X2X1,5 | 12,1 | 37 | 2,515 |
| 2X2,5 | 12,1 | 13,2 | 0,369 |
| 3X2,5 | 12,1 | 13,7 | 0,406 |
*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.