ROZ1MZ1(AS+)-KX

ROZ1MZ1(AS+)-KX

A Thermocouple is a device that produces a signal for measuring temperature. The signal is created when two dissimilar metals have heat applied to them. Thermocouple Extension Cables allow the signal created by the Thermocouple to reach the controller or monitoring device. These cables are indicated for industrial installations with a risk of fire and explosion. It can be used in installations as production plants and in general in all the installations where the cable can be subject to risks interferences, mechanical aggression and greater fire protection is required.

  • Technical designation ROZ1MZ1(AS+)
  • KX type: conductor Chromel (+) / Alumel (-).
  • Construction Standard: IEC 60584.
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Cca-s1b, d1, a1.
  • DoP Number: C019-ENG-ROZ1MZ1KXMICA.
  • RoHS compliant.
  • Suitable for Industrial use / Potentially explosion hazard locations (ATEX area).
  • Maximum fire resistant PH120.

Conductor: KX type: Chromel (+) / Alumel (-).
Insulation: Cross-linked Polyethylene (XLPE) + mica tape.
Screen (individual/overall): Individual polyester composed by on aluminum / polyester tape with 100% coverage + tinned copper drain wire.
Inner sheath: Low Smoke Zero Halogen (LSZH) polyolefin.
Armour: Crown galvanized steel wire
Outer sheath: Low Smoke Zero Halogen (LSZH) polyolefin.
Voltage Test: 500 V C.A.
Maximum conductor temperatures: Normal operation 90°C (105°C). Short circuit (5sec) 160°C

  • Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
  • Non-fire propagation according to EN 60332-3-24, IEC 60332-3-24.
  • Low halogen content according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.
  • Low corrosive gas emission according to EN 60754-2, IEC 60754-2.
  • Low smoke emission according to EN 61034-2, IEC 61034-2.
  • Fire reaction (CPR) Cca-s1b, d1, a1.
  • Fire resistance PH120 (840°C, 120 minutes) according UNE-EN 50200
  • UV resistance (1 cycle) according to UNE 211605.
  • Water absorption resistance.
  • High cold resistance.
  • Impact and rodent resistance.

Available on request

  • Hydrocarbons and oil resistance according to UIC-895 OR.
Section (mm2)

Loop resistance at 20 °C

(Ohm/km)

Nominal outer diameter (mm) Weight (kg/m) CPR
2X1,3 767 12,8 0,33 Cca-s1b-d1-a1

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.