RVFAV / RVFAV-K

RVFAV / RVFAV-K

RVFAV / RVFAV-K cables have been specially designed for fixed installations that may be subject to mechanical aggression. It is highly recommended for use in installations where the presence of rodents could imply a threat to the cable. It can be used in installations such as production plants, agricultural facilities, street lighting and installations in general where the cable is subject to high mechanical aggression.

  • Technical designation RVFAV rigid copper conductor class 2.
  • Technical designation RVFAV-K flexible copper conductor class 5.
  • Construction Standard: IEC 60502-1, UNE 21123-2
  • Low Voltage Directive (LVD) compliant: 2014/35/UE
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Eca.
  • DoP Number: E010-ENG-RVFAV
  • DoP Number: E011-ENG-RVFAVK
  • RoHS compliant.

Conductor: Rigid electrolytic copper conductor (Class II) or flexible (class V) according to UNE-EN 60288.
Insulation: Cross-linked Polyethylene (XLPE), type DIX 3 according UNE 21123, UNE HD 603 and XLPE according IEC 60502.
Armour: PVC DMV-18 type according to UNE 21123-2 and ST2 type according to IEC 60502-1.
Inner sheath: Double aluminium tape armour.
Outer sheath: PVC DMV-18 type according to UNE 21123-2 and ST2 type according to IEC 60502-1.
Nominal Voltage: 0,6/1 kV C.A.
Voltage Test: 3.500 V C.A.
Maximum conductor temperatures: Normal operation 90°C. Short circuit (5sec) 250°C.

  • Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
  • Fire reaction (CPR) Eca.
  • UV resistance (1 cycle) according to UNE 211605.
  • Suitable for all type of installations withstand damp conditions including total immersion in water (AD7).
  • High cold resistance, cable designed to operate reliably at -40ºC in fixed installations and protected installations.
  • Impact resistance: AG4. High severity.
  • Rodent resistance.

Available on request

  • Hydrocarbons and oil resistance according to UIC-895 OR.
  • Non-fire propagation according to EN 60332-3-24, IEC 60332-3-24.
  • Low halogen content (≤ 14%) according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.

(RVFAV rigid copper conductor class 2)

Section (mm2) Resistance at 20 °C

(Ohm/km)

Nominal outer diameter (mm) Weight (kg/m) CPR
1×16 1,15 14,1 0,372 Eca
1×25 0,727 15,7 0,496 Eca
1×35 0,524 16,9 0,622 Eca
1×50 0,387 18,5 0,771 Eca
1×70 0,268 19,9 0,982 Eca
1×95 0,193 21,6 1,258 Eca
1×120 0,153 23,4 1,534 Eca
1×150 0,124 25,1 1,816 Eca
1×185 0,0991 28,7 2,350 Eca
1×240 0,0754 31,6 2,954 Eca
1×300 0,0601 34,7 3,632 Eca
1×400 0,047 38,7 4,694 Eca
1×500 42,6 5,833 Eca

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.