RVFV / RVFV-K cables have been specially designed for fixed installations that may be subject to mechanical aggression. It is highly recommended for use in installations where the presence of rodents could imply a threat to the cable. It can be used in installations such as production plants, agricultural facilities, street lighting and installations in general where the cable is subject to high mechanical aggression.

  • Technical designation RVFV rigid copper conductor class 2.
  • Technical designation RVFV-K flexible copper conductor class 5.
  • Construction Standard: IEC 60502-1, UNE 21123-2
  • Low Voltage Directive (LVD) compliant: 2014/35/UE
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Eca.
  • DoP Number: E008-ENG-RVFAV
  • DoP Number: E009-ENG-RVFAVK
  • RoHS compliant.

Conductor: Rigid electrolytic copper conductor (Class II) or flexible (class V) according to UNE-EN 60288
Insulation: Cross-linked Polyethylene (XLPE), type DIX 3 according UNE 21123, UNE HD 603 and XLPE according IEC 60502.
Armour: PVC DMV-18 type according to UNE 21123-2 and ST2 type according to IEC 60502-1.
Inner sheath: Double steel tape armour.
Outer sheath: PVC DMV-18 type according to UNE 21123-2 and ST2 type according to IEC 60502-1.
Nominal Voltage: 0,6/1 kV C.A.
Voltage Test: 3.500 V C.A.
Maximum conductor temperatures: Normal operation 90°C. Short circuit (5sec) 250°C

  • Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
  • Fire reaction (CPR) Eca.
  • UV resistance (1 cycle) according to UNE 211605.
  • Suitable for all type of installations withstand damp conditions including total immersion in water (AD7).
  • High cold resistance, cable designed to operate reliably at -40ºC in fixed installations and protected installations.
  • Impact resistance: AG4. High severity.
  • Rodent resistance.

Available on request

  • Hydrocarbons and oil resistance according to UIC-895 OR.
  • Non-fire propagation according to EN 60332-3-24, IEC 60332-3-24.
  • Low halogen content (≤ 14%) according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.

(RVFV rigid copper conductor class 2)

Section (mm2) Resistance at 20 °C

(Ohm/km)

Nominal outer diameter (mm) Weight (kg/m) CPR
2×1.5 12,1 12,6 0,266 Eca
3×1.5 12,1 13,0 0,290 Eca
4×1.5 12,1 13,8 0,327 Eca
5×1.5 12,1 14,6 0,364 Eca
7×1.5 12,1 15,5 0,424 Eca
10×1.5 12,1 18,4 0,554 Eca
12×1.5 12,1 18,8 0,600 Eca
14×1.5 12,1 19,6 0,658 Eca
16×1.5 12,1 20,4 0,715 Eca
19×1.5 12,1 21,3 0,793 Eca
24×1.5 12,1 24,2 0,961 Eca
30×1.5 12,1 25,4 1,103 Eca
37×1.5 12,1 27,1 1,276 Eca
44×1.5 12,1 30,2 1,495 Eca
2×2.5 7,41 13,6 0,315 Eca
3×2.5 7,41 14,1 0,349 Eca
4×2.5 7,41 15,0 0,397 Eca
5×2.5 7,41 16,0 0,448 Eca
7×2.5 7,41 17,0 0,529 Eca
10×2.5 7,41 20,4 0,701 Eca
12×2.5 7,41 20,9 0,767 Eca
14×2.5 7,41 21,8 0,845 Eca
16×2.5 7,41 22,8 0,926
19×2,5 7,41 23,8 1,035
24×2.5 7,41 27,2 1,261
30×2.5 7,41 28,8 1,477
37×2.5 7,41 30,8 1,722
44×2.5 7,41 34,6 1,973
2×4 4,61 14,6 0,377
3×4 4,61 15,2 0,427
4×4 4,61 17,2 0,492
5×4 4,61 17,3 0,561
7×4 4,61 18,5 0,677
10×4 4,61 22,4 0,908
12×4 4,61 23,0 1,007
2×6 3,08 15,6 0,443
3×6 3,08 16,3 0,510
4×6 3,08 17,4 0,594
5×6 3,08 18,7 0,837
2×10 1,83 17,0 0,566
3×10 1,83 17,9 0,669
4×10 1,83 10,1 0,794
5X10 1,83 20,6 0,837
2×16 1,15 19,0 0,745
3×16 1,15 19,9 0,899 Eca
4×16 1,15 21,5 1,084 Eca
5×16 1,15 23,3 1,278 Eca
2×25 0,727 22,2 1,049 Eca
3×25 0,727 23,4 1,289 Eca
4×25 0,727 25,4 1,57 Eca
5×25 0,727 27,6 1,921 Eca
2×35 0,524 24,6 1,337 Eca
3×35 0,524 25,9 1,660 Eca
4×35 0,524 28,2 2,039 Eca
5×35 0,524 31,1 2,518 Eca
2×50 0,387 27,8 1,728 Eca
3×50 0,387 29,6 2,180 Eca
4×50 0,387 32,9 2,739 Eca
5×50 0,387 36,2 3,378 Eca
2×70 0,268 30,8 2,244 Eca
3×70 0,268 33,2 2,905 Eca
4×70 0,268 36,5 3,624 Eca
5×70 0,268 40,1 4,534
2×95 0,193 35,8 2,996
3×95 0,193 37,2 3,829
4×95 0,193 41,0 4,803
5×95 0,193 45,1 6,007
2×120 0,153 38,8 3,712
3×120 0,153 41,3 4,762
4×120 0,153 45,9 6,030
5×120 0,153 50,4 7,565
2×150 0,124 42,4 4,449
3×150 0,124 45,6 5,772
4×150 0,124 49,6 7,174
2×185 0,0991 50,6 5,972
3×185 0,0991 53,7 7,671
4×185 0,0991 59,7 9,698
2×240 0,0754 57,2 7,642
3×240 0,0754 66,8 12,335

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.