RZ1C7Z1MZ1-K(AS)

RZ1C7Z1MZ1-K(AS)

HFFR, screened and armoured cables RZ1C7Z1MZ1-K(AS) are highly recommended in hazardous areas with explosive gas atmospheres (ATEX) or with risk of fire (Petrochemical plants, gas stations, flammable product stores, etc.) and in general, where the cable is subject to risk of mechanical aggression. Furthermore, when it is necessary to avoid the interferences that the power supply could cause in adjacent signal transmission cables.

  • Construction Standard: IEC 60502-1, UNE 21123-4
  • Low Voltage Directive (LVD) compliant: 2014/35/UE
  • Construction Products Regulation (CPR) – (EU) Nº 305/2011: Reaction to fire Cca-s1b, d1, a1.
  • DoP Number: C021-ENG- RZ1C7Z1MZ1K(AS)
  • RoHS compliant.
  • Suitable for Industrial use / Potentially explosion hazard locations (ATEX area).

Conductor: Flexible electrolytic copper conductor (Class V) according to UNE-EN 60288 and IEC 60228
Insulation: Cross-linked Polyethylene (XLPE), type DIX 3 according UNE 21123, UNE HD 603 and XLPE according IEC 60502.
1º Inner sheath: Thermoplastic polyolefin sheath DMZ-E type according to UNE 21123 and ST8 according to IEC 60502-1
Screen: Copper strip.
2º Inner sheath: Thermoplastic polyolefin sheath DMZ-E type according to UNE 21123 and ST8 according to IEC 60502-1.
Armour: Crown galvanized steel wire according to IEC 60502-1 and UNE 21123-4
Outer sheath: Thermoplastic polyolefin sheath DMZ-E type according to UNE 21123 and ST8 according to IEC 60502-1.
Nominal Voltage: 0,6/1 kV C.A
Voltage Test: 3.500 V C.A.
Maximum conductor temperatures: Normal operation 90°C. Short circuit (5sec) 250°C

  • Non-flame propagation according to EN 60332-1-2, IEC 60332-1-2.
  • Non-fire propagation according to EN 60332-3-24, IEC 60332-3-24.
  • Low halogen content according to EN 60754-2, EN 60754-1, IEC 60754-2, IEC 60754-1.
  • Low corrosive gas emission according to EN 60754-2, IEC 60754-2.
  • Low smoke emission according to EN 61034-2, IEC 61034-2.
  • Fire reaction (CPR) Cca-s1b, d1, a1.
  • UV resistance (1 cycle) according to UNE 211605.
  • Water absorption resistance.
  • High cold resistance.
  • Impact and rodent resistance.

Available on request

  • Hydrocarbons and oil resistance according to UIC-895 OR.
Section (mm2) Resistance at 20 °C

(Ohm/km)

Nominal outer diameter (mm) Weight (kg/m) CPR
2×4 4,95 19,4 0,776 Cca-s1b-d1-a1
2X6 3,3 20,6 0,883 Cca-s1b-d1-a1
2×10 1,91 20,6 1,187 Cca-s1b-d1-a1
2×16 1,21 25,3 1,436 Cca-s1b-d1-a1
2×25 0,78 28,7 1,817 Cca-s1b-d1-a1
3×2,5 7,98 18,5 0,715 Cca-s1b-d1-a1
3×4 4,95 19,6 0,806 Cca-s1b-d1-a1
3×6 3,3 20,9 0,929 Cca-s1b-d1-a1
3×10 1,91 23,5 1,284 Cca-s1b-d1-a1
3×16 1,21 25,9 1,579 Cca-s1b-d1-a1
3×25 0,78 29,5 2,089 Cca-s1b-d1-a1
4×4 4,95 20,6 0,898 Cca-s1b-d1-a1
4×6 3,3 23,2 1,197 Cca-s1b-d1-a1
4X10 1,91 24,9 1,443 Cca-s1b-d1-a1
4×16 1,21 28 1,851 Cca-s1b-d1-a1
4×25 0,78 32,3 2,441 Cca-s1b-d1-a1
6×6 3,3 25,9 1,498 Cca-s1b-d1-a1
10×2,5 7,98 25,6 1,342 Cca-s1b-d1-a1

 

*The values of the outer diameters are approximate, always within production tolerance. For more information, please contact us.